Cornell 4000 D-112 Duty stations
- INFO
- SPECS
- RELATED
Cornell 4000 D-112 Duty stations
Duty stations serve as a remote notification to the staff that a call for assistance has been made in their area.
D-112 Duty Station
The D-112 Duty Station indicates normal calls with a steady green LED and slow intermittent tone. Emergency calls are indicated with flashing red LED and rapid tone.
Technical Information:
- Power Requirements: 24VDC
- Operating Environment: 50-120°F Indoor Non-condensing
- Physical Faceplate Dimensions: 4 1⁄2 ”H x 2 3⁄4 ”W (Standard 1 Gang)
- Mounting: Single-Gang back box with 13⁄4” minimum depth
- Wiring: #22 AWG Minimum, #16 AWG Maximum
D-111 and D-112:
Mounting:
The satin finish stainless steel faceplates with silk-screened designations may be flush mounted on a standard outlet box with a single-gang plaster ring or surface mounted on a Wiremold 5748 or equivalent. Field wiring terminations are with screw clamps, with a maximum of 16 gauge wire.
Engineering Specifications:
The contractor shall furnish and install CORNELL Duty Stations (D-111) or (D-112) as indicated on the plans. Flashing red LED and rapid intermittent tone shall indicate an emergency call; steady green LED and slow tone shall indicate a normal call. Incandescent lamps are not acceptable. The station shall fit on a standard single-gang plaster ring or Wiremold 5748 surface box or equivalent, with a minimum depth of 1 3⁄4” required. Terminations for field wiring shall be with screw clamps.
SKU D-112 UPC 351309470880 Condition New Manufacturer Cornell