img3

Cornell S-111 - Staff Station E-104-1 & D-111 on a Two Gang Plate

SKU
S-111
$246.00

Cornell S-111 Staff Station with Tone On/Off Switch.

Cornell Area of Refuge Quote

OR
  • INFO
  • SPECS
  • RELATED
  • REVIEWS
  • Description:

    The Cornell S-111 Staff Station includes an on/off tone switch that can be passed, green LED to indicate normal call, and red LED to indicate emergency call. The S-111 Staff station is also furnished with a pullstring to place a call on the system.

    Operation:

    The S-111 Staff Station has a tone on-off switch that is provided to silence the audible alert by staff. Normal calls are indicated with a steady green LED and slow intermittent tone. Emergency calls are indicated with flashing red LED and rapid tone. To place calls on the system, pull cord; the station’s red LED, and associated corridor and annunciator panel lights, are illuminated, and a tone sounds at the annunciator panel. To cancel, slide switch to off position.

    Mounting:

    The satin finish stainless steel faceplate with silk-screened designations may be flush mounted on a standard outlet box with two-gang plaster ring, or surface mounted on a Wiremold 5748 or equivalent. Field wiring terminations are with screw clamps, maximum 16 gauge.

    Engineering Specifications:

    The contractor shall furnish and install a CORNELL Clinical Staff Station S-111 or S-112. Incoming emergency calls shall be indicated by flashing red LED and rapid intermittent tone; normal calls, by steady green LED and slow intermittent tone; priority calls via pulsing red LED and pulsing tone. Incandescent lamps are not acceptable. Pulling of cord shall illuminate the call placed indicator and associated corridor and annunciator lights, and cause an intermittent tone at the annunciator panel. The stainless steel face-plate shall have silk-screened designations and shall fit on a standard two-gang plaster ring or Wiremold 5748-2 surface box or equal, with minimum depth of 1 ¾”. Field wiring terminations shall be with wire screw clamps.

    Technical Information:

    • Power Requirements: 24VDC
    • Operating Environment: 50-120°F Indoor Non-condensing
    • Physical Faceplate Dimensions: 4 ½ ”H x 4 ½ ”W (Standard 2 Gang)
    • Mounting: Two-Gang back box with 1¾” minimum depth
    • Wiring: #22 AWG Minimum, #16 AWG Maximum  

    Cornell Area of Refuge Quote